SW1

The dialing code mainly controls and selects the

type of unit. It is suggested to adjust under the

guidance of the engineering sta.

SW1-1: Switch communication mode function,

(ON: 24V wire controller; OFF: non-24V wire

controller, default)

SW1-2: This dial code can be used to set whether

to stop the fan when the cold air is released, OFF

stops the fan, ON does not stop the fan, default

OFF

SW1-3: Select single cold and heat pump functions.

ON: single cooling; OFF: heating and cooling,

default

SW1-4: The dialing function is to select indoor and

outdoor unit or indoor unit. The default OFF means

the indoor and outdoor unit, at this time you need

to connect the outdoor unit equipped with the

AHU set. When the user uses the temperature

control to control the indoor and outdoor unit,

they need to switch the dialing code to ON, which

means the independent indoor unit; at this time,

the indoor unit module does not communicate

with the outdoor unit, and does not process the

information of the outdoor unit. The wire controller

cannot be used, it needs to be connected to a

24V thermostat.

SW2

This dial code mainly controls the opening

form of the electric auxiliary heat.

SW2-1: This dial code can control the temperature

difference when the electric heating is turned on.

OFF: 2°C, default; ON: 1°C, 3-level temperature

setting, consistent with user thermostat setting.

Note: When E/AUX controls electric heating,

there is no temperature dfference, and it starts

directly

SW2-2, SW2-3: This two-digit dialing code can

control the delayed start of electrically-assisted

heat.

When the temperature difference is too large,

the delayed start and the delayed start time can

be selected.

SW2-2

1-bit dialing, ON 2.5°C,

OFF without delay

SW2-3

1 bit dialing, OFF 15 minutes,

ON 30 minutes, 15 minutes by

default, delayed opening time

SW2-4: This dial code controls the allowable

opening temperature of electric heating or

compressor, OFF allows the opening temperature

of electric heating (using the set temperature of

S3 as the upper limit temperature of electric

heating), and ON the allowable opening

temperature of the compressor (using S3 as the

upper limit temperature of electric heating). The

lower limit temperature at which the compressor

can allow operation.)

 SW3

Ambient temperature controlled by electric

heating or compressor, 0 means no temperature

protection is turned on, 1-F is -20-8°C, and each

scale represents 2°.

SW3-1

This dialing code can set the continuous operation

time of increasing the set temperature by 0.5°C~3°C

before reaching the temperature. The default is

OFF 1.5h, ON 30min.

SW3-2

This dialing code can set Y/Y2 signal setting

temperature adjustment deviation, ON: 1°C;

OFF: 2 ° C.

SW3-3

This dialing code can set W2 signal setting

temperature adjustment deviation, ON: 2°C;

OFF: 3 ° C.


STATIC PRESSURE DIP SWITCH

SW4

This dialing code is only valid for 1-3. Composition

of binary code, respectively corresponding to

dierent wind prole static pressure.

000 is the default; 000/001/010/011/100/101/110/

111, with dierent capacities of indoor unit and

electric heating and PSC for selection and use,

corresponding to dierent air volumes, see air

volume table for details.